NEC requirement
Services that supply the following are required to have surge protection installed within the service equipment:
1. Dwelling units
2. Dormitory units
3. Guest rooms and guest suites of hotels and motels
4. Areas of nursing homes and limited-care facilities used exclusively as patient sleeping rooms
There is an exception that permits surge protection to not be installed in service equipment—when surge protection is installed in the next-level distribution equipment downstream toward the load.
In addition to the requirements for services, there are also requirements for feeder applications. Equipment that supplies the same occupancy types listed in 230.67 that is not service equipment but fed from a feeder is also required to be equipped with a surge protective device (SPD). Sections 215.18 and 225.42 address feeder applications.
NEC 2023 code change/intention